I/O Ports (GPIO)
    • 31 Mar 2023
    • 1 Minute to read
    • Dark
      Light
    • PDF

    I/O Ports (GPIO)

    • Dark
      Light
    • PDF

    Article summary

    Nodegrid Gate SR supports two digital I/O ports (DIO0, DIO1), one digital output port (OUT0) and one relay port (1A@24V).

    Nodegrid Link SR supports two digital I/O ports (DIO0, DIO1) and two digital output ports (OUT0, OUT1).

    DIO0 and DIO1 can be independently configured as input or output. The DIO0 and DIO1 are open-drain digital I/O ports with TTL level (5.5V max @ 64mA). ESD protection exceeds JESD 22.

    When DIO port is configured as input:

    contact is open, senses High (1)
    contact is closed, senses Low (0)

    NOTE
    DIO0 and DIO1 port configuration as input is ideal for dry contact applications (door close, vibration, water, smoke sensors).

    When DIO port is configured as output:

    set to high, outputs TTL high
    set to low, outputs TTL low

    NOTE
    DIO0 and DIO1 port configuration as output can control low voltage/current applications.

    The OUT0 and OUT1 are high voltage digital outputs. Each port is internally attached to a Signal MOSFET. The output port is normally open (NO) and capable of supporting a voltage range from 2.5V to 60V @ 500mA.

    When OUT port is set to:

    High (enabled/active and pulls OUT to ground)
    Low (disabled/inactive and keeps OUT open)

    NOTE
    OUT0 and OUT1 can pull a power-connected line to ground (i.e., relay circuit).

    On Nodegrid Gate SR, the RELAY port is normally a closed (NC) relay (rated max value of 24V @ 1A). The RELAY specification supports a maximum switching power of 60W, 125VA; maximum switching voltage of 220VDC, 250VAC; maximum switching current of 2A, with restive load.

    The RELAY’s primary function is a Power Source Control Alarm. When closed, it indicates that Nodegrid Gate SR is powered by a single power source or has no power. If the Nodegrid Gate SR is powered by both power input sources, when RELAY is closed, it indicates a FAILURE on at least one power input sources.

    (optional), RELAY can be changed to follow software control (Open / Close), to control an external device. Possible relay states are:

    open (opens relay contact)
    close (closes relay contact)

    The I/O Port configuration is under System :: I/O Ports. I/O Port status and other hardware details is under Tracking :: HW Monitor.

    WARNING!
    For Safety Reasons, do not exceed max voltage or current defined on each port.